Asphalt shingles shall be fastened to solidly sheathed decks. For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s. Wood shingles shall be laid with a side lap not less than 1, NAIL REQUIREMENTS FOR WOOD SHAKES AND WOOD SHINGLES, Roof flashing shall be not less than No. Spray-applied polyurethane foam insulation shall comply with ASTM C1029, Type III or IV or ASTM D7425. Liquid-applied roofing shall have a design. redundant requirements for stud nailing, and create consistency in the IRC for roof sheathing attachment. Liquid-applied roofing shall be installed in accordance with this chapter and the, Where required, an ice barrier shall comply with, In areas where there has been a history of ice forming along the eaves causing a backup of water, as designated in, The use of above-deck thermal insulation shall be permitted provided that such insulation is covered with an. Each bundle of shakes shall be identified by a. Section R803 Roof Sheathing R803.2 Wood Structural Panel Sheathing (Roof Online Note: This subsection covers plywood and OSB sheathing. Minimum headlap for slate shingles shall be in accordance with Table R905.6.5. Cap nail shank shall have a length sufficient to penetrate through the roof sheathing or not less than, The standard calculations contained in ASTM D7158 assume Exposure Category B or C and a. Interlayment shall comply with ASTM D226, Type I. Base flashing against a vertical sidewall shall be continuous or step flashing and shall be not less than 4 inches (102 mm) in height and 4 inches (102 mm) in width and shall direct water away from the vertical sidewall onto the roof or into the gutter. hbbd```b``3@$R&5d}"uA$$X ,>,rLYfH 2o2dbO C"=Vbz CHEX/#300 k Copper, brass, bronze, copper alloy and 300-series stainless steel fasteners shall be used for copper roofs. Where siding is provided on the vertical sidewall, the vertical leg of the flashing shall be continuous under the siding. Flashing for asphalt shingles shall comply with this section. For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s. Same as Maximum Ultimate Design Wind Speed, Asphalt-saturated and asphalt-coated organic felt base sheet, Asphalt-saturated organic felt (perforated), Coal-tar primer used in roofing, dampproofing and waterproofing, ASTM B370 minimum 16 oz/sq ft and 12 oz/sq ft high-yield copper for metal-sheet. R905.2.2 Slope. or less, R905.2.4.1 Wind Resistance of Asphalt Shingles, R905.14 Sprayed Polyurethane Foam Roofing, R905.17 Building-Integrated Photovoltaic (BIPV) Roof Panels Applied Directly to the Roof Deck, Section R907 Rooftop-Mounted Photovoltaic Panel Systems, R907.1 Rooftop-Mounted Photovoltaic Panel Systems, Building-integrated photovoltaic products. The installation of mineral-surfaced roll roofing shall comply with this section. For closed valleys (valley covered with shingles), valley lining of one ply of smooth roll roofing complying with ASTM D6380 and not less than 36 inches wide (914 mm) or valley lining as described in Item 1 or 2 shall be permitted. 12 oz/sq ft for preformed metal shingle systems. Valley linings of the following types shall be permitted: For SI: 1 inch = 25.4 mm, 1 pound = 0.454 kg. The framing assembly incudes horizontal braces, vertical retrofit studs, and compression blocks. Stainless steel fasteners are acceptable for metal roofs. Asphalt shingles shall be fastened to solidly sheathed decks. Flashing and counterflashing shall be made with sheet metal. Roof valley flashing shall be not less than No. Install flashing at roof penetrations and wall intersections. Valley linings shall be installed in accordance with the manufacturer's instructions before applying shingles. The installation of wood shingles shall comply with the provisions of this section. CONTINUE WITH CODE REQ'S Mineral-surfaced roll roofing shall be fastened to solidly sheathed roofs. 3. For open valleys (valley lining exposed) lined with metal, the valley lining shall be not less than 24 inches (610 mm) wide and of any of the corrosion-resistant metals in Table R905.2.8.2. The installation of asphalt shingles shall comply with the provisions of this section. Same as Maximum Ultimate Design Wind Speed, Preservative-treated shakes and shingles of, Fire-retardant-treated shakes and shingles of, Preservative-treated tapersawn shakes of Southern pine treated in accordance with AWPA Standard U1 (Commodity Specification A, Special Requirement 4.6), Forest Products Laboratory of the Texas Forest Services, Preservative-treated tapersawn shakes of Southern Yellow Pine, Asphalt-saturated and asphalt-coated organic felt base sheet, Asphalt-saturated organic felt (perforated), Coal-tar primer used in roofing, dampproofing and waterproofing, ASTM B370 minimum 16 oz/sq ft and 12 oz/sq ft high-yield copper for metal-sheet. Where the existing roof covering is slate, clay, cement or asbestos-cement tile. Galvanized fasteners shall be used for steel roofs. Thermoplastic single-ply roofs shall be installed in accordance with this chapter and the manufacturer's instructions. 2015 IRC portion of the 2018 CT State Building Code, Part III Building Planning and Construction, R907 Rooftop-Mounted Photovoltaic Systems, R909 Rooftop-Mounted Photovoltaic Panel Systems, Chapter 13 General Mechanical System Requirements, Chapter 14 Heating and Cooling Equipment and Appliances, Chapter 19 Special Appliances, Equipment and Systems, Chapter 22 Special Piping and Storage Systems, Chapter 37 Branch Circuit and Feeder Requirements, Chapter 39 Power and Lighting Distribution, Chapter 43 Class 2 Remote-Control, Signaling and Power-Limited Circuits, Appendix A Sizing and Capacities of Gas Piping, Appendix B Sizing of Venting Systems Serving Appliances Equipped With Draft Hoods, Category I Appliances, and Appliances Listed for Use With Type B Vents, Appendix C Exit Terminals of Mechanical Draft and Direct-Vent Venting Systems, Appendix D Recommended Procedure for Safety Inspection of an Existing Appliance Installation, Appendix E Manufactured Housing Used as Dwellings, Appendix G Piping Standards for Various Applications, Appendix J Existing Buildings and Structures, Appendix T Recommended Procedure for Worst-Case Testing of Atmospheric Venting Systems Under N1102.4 or N1105 Conditions 5ACH, Appendix U Solar-Ready ProvisionsDetached One- And Two-Family Dwellings, Multiple Single-Family Dwellings (Townhouses), Appendix V Wind Speeds, Seismic Design Categories and Ground Snow Loads, The provisions of this chapter shall govern the design, materials, construction and quality of, Roofs shall be covered with materials as set forth in Sections, Flashings shall be installed in a manner that prevents moisture from entering the wall and roof through joints in copings, through moisture permeable materials and at intersections with parapet, Flashings shall be installed at wall and roof intersections, wherever there is a change in roof, A cricket or saddle shall be installed on the ridge side of any, The requirements set forth in this section shall apply to the application of, For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, In areas where there has been a history of ice forming along the eaves causing a backup of water as designated in. Copper, brass, bronze, copper alloy and 300-series stainless steel fasteners shall be used for copper roofs. The installation of thermoset single-ply roofing shall comply with the provisions of this section. The installation of sprayed polyurethane foam roofing shall comply with the provisions of this section. 26 gage [0.019 inch (0.5 mm)] corrosion-resistant sheet metal and shall extend not less than 11 inches (279 mm) from the centerline each way. For open valleys (valley lining exposed) lined with metal, the valley lining shall be not less than 24 inches (610 mm) wide and of any of the corrosion-resistant metals in Table R905.2.8.2. Asphalt shingles shall be tested in accordance with ASTM D7158. Same as Maximum Ultimate Design Wind Speed, Apply in accordance with the manufacturer's, Asphalt-saturated and asphalt-coated organic felt base sheet, Asphalt-saturated organic felt (perforated), Coal-tar primer used in roofing, dampproofing and waterproofing, ASTM B 370 minimum 16 oz/sq ft and 12 oz/sq ft high-yield copper for metal-sheet, ASTM B 209, 0.024 minimum thickness for roll-formed panels and 0.019-inch minimum, Terne coating of 40 lb per double base box, field painted where applicable in accordance with, 0.027 inch minimum thickness: 99.995% electrolytic high-, As an alternative, self-adhering polymer-modified bitumen, The standard calculations contained in ASTM D 7158 assume Exposure Category B or C and. A liquid-applied protective coating that complies with Table R905.14.3 shall be applied not less than 2 hours nor more than 72 hours following the application of the foam. Slate shingles shall be installed in accordance with this chapter and the manufacturer's instructions. Foamed-in-place roof insulation shall be installed in accordance with this chapter and the manufacturer's instructions. The installation of slate shingles shall comply with the provisions of this section. R905.2.4.1 Wind Resistance of Asphalt Shingles, R905.14 Sprayed Polyurethane Foam Roofing, Section R907 Rooftop-Mounted Photovoltaic Systems, R907.1 Rooftop-Mounted Photovoltaic Systems, Section R909 Rooftop-Mounted Photovoltaic Panel Systems, Building-integrated photovoltaic products. 2018, 2021 IECC: Mass walls shall be in accordance with Section R402.2.5 (N1102.2.5 in 2018 IRC). A liquid-applied protective coating that complies with Table 905.14.3 shall be applied not less than 2 hours nor more than 72 hours following the application of the foam. Wood shakes shall be installed in accordance with this chapter and the, The starter course at the eaves shall be doubled and the bottom layer shall be either 15-inch (381 mm), 18-inch (457 mm) or 24-inch (610 mm) wood shakes or wood shingles. In areas where the average daily temperature in January is 25F (-4C) or less, Wood shingles shall be installed in accordance with this chapter and the manufacturer's instructions. Fifteen-inch (381 mm) or 18-inch (457 mm) wood shakes shall be permitted to be used for the final course at the. Asphalt shingle packaging shall bear a. For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s. The bottom layer shall be 18 inches (457 mm) and the top layer not less than 36 inches (914 mm) wide. 2 RESIDENTIAL ROOFING GUIDE 2018 IRC. Asphalt shingle packaging shall bear a. Roof valley flashing shall be not less than No. Fasteners for asphalt shingles shall be galvanized steel, stainless steel, aluminum or copper roofing nails, minimum 12-gage [0.105 inch (3 mm)] shank with a minimum 3 / 8 -inch- diameter (9.5 mm) head, complying with ASTM F1667, of a length to penetrate through the roofing materials and not less than 3 / 4 inch (19.1 mm) into the roof sheathing. Reroofing shall not be required to meet the minimum design, For roofs that provide positive drainage, recovering or replacing an existing, Complete and separate roofing systems, such as standing-seam metal roof systems, that are designed to transmit the roof loads directly to the building's structural system and do not rely on existing roofs and, Where the existing roof has two or more applications of any type of. Modified bitumen roofing shall comply with the standards in Table R905.11.2. Slate shingles shall comply with ASTM C406. 2. The installation of wood shakes shall comply with the provisions of this section. The installation of sprayed polyurethane foam roofing shall comply with the provisions of this section. Section R901 General R901.1 Scope The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. Modified bitumen roofing shall comply with the standards in Table R905.11.2. The installation of built-up roofs shall comply with the provisions of this section. Slate shingles shall be secured to the roof with two fasteners per slate. Part III Building Planning and Construction, R907 Rooftop-Mounted Photovoltaic Panel Systems, Chapter 13 General Mechanical System Requirements, Chapter 14 Heating and Cooling Equipment and Appliances, Chapter 19 Special Appliances, Equipment and Systems, Chapter 22 Special Piping and Storage Systems, Chapter 37 Branch Circuit and Feeder Requirements, Chapter 39 Power and Lighting Distribution, Chapter 43 Class 2 Remote-Control, Signaling and Power-Limited Circuits, Appendix A Sizing and Capacities of Gas Piping, Appendix B Sizing of Venting Systems Serving Appliances Equipped With Draft Hoods, Category I Appliances and Appliances Listed for Use With Type B Vents, Appendix C Exit Terminals of Mechanical Draft and Direct-Vent Venting Systems, Appendix D Recommended Procedure for Safety Inspection of an Existing Appliance Installation, Appendix E Manufactured Housing Used as Dwellings, Appendix G Piping Standards for Various Applications, Appendix J Existing Buildings and Structures, Appendix T [RE] Solar-Ready ProvisionsDetached One- And Two-Family Dwellings and Townhouses, The provisions of this chapter shall govern the design, materials, construction and quality of, Roofs shall be covered with materials as set forth in Sections, Flashings shall be installed in a manner that prevents moisture from entering the wall and roof through joints in copings, through moisture permeable materials and at intersections with parapet, Flashings shall be installed at wall and roof intersections, wherever there is a change in roof, A cricket or saddle shall be installed on the ridge side of any, The requirements set forth in this section shall apply to the application of, ASTM D6380 Class M mineral-surfaced roll roofing. Wood shakes shall be installed in accordance with this chapter and the, The starter course at the eaves shall be doubled and the bottom layer shall be either 15-inch (381 mm), 18-inch (457 mm) or 24-inch (610 mm) wood shakes or wood shingles. Brace gable end walls taller than 48. inches in height to resist wind forces by installing a framing assembly at each gable wall stud. Galvanized fasteners shall be used for steel roofs. R905.2.1 Sheathing requirements. 26 gage [0.019 inches (0.5 mm)] corrosion-resistant sheet metal and shall extend 10 inches (254 mm) from the centerline each way for roofs having, Each bundle of shingles shall be identified by a. Drip edges shall extend not less than. If re-roofing over wood shingle, or wood shake roofs, additional code requirements may apply. . For the most common roof sheathing in our area, which is 1/2" nominal (7/16" actual) sheathing over trusses or rafters at 24" on center . The installation of asphalt shingles shall comply with the provisions of this section. Mineral-surfaced roll roofing shall conform to ASTM D 3909 or ASTM D 6380, Class M. Mineral-surfaced roll roofing shall be installed in accordance with this chapter and the manufacturer's instructions. Fasteners for asphalt shingles shall be galvanized steel, stainless steel, aluminum or copper roofing nails, minimum 12-gage [0.105 inch (3 mm)] shank with a minimum -inch-diameter (9.5 mm) head, complying with ASTM F1667, of a length to penetrate through the roofing materials and not less than inch (19.1 mm) into the roof sheathing. Copper, brass, bronze, copper alloy and 300-series stainless steel fasteners shall be used for copper roofs. A base sheet that complies with the requirements of. Spray-applied polyurethane foam insulation shall comply with ASTM C1029, Type III or IV or ASTM D7425. Wood shakes shall comply with the requirements of Table R905.8.5. For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s. Asphalt shingles shall comply with ASTM D3462. Asphalt shingles shall meet the classification requirements of Table R905.2.4.1 for the appropriate ultimate design wind speed. Asphalt shingles shall meet the classification requirements of Table R905.2.4.1 for the appropriate ultimate design wind speed. Asphalt shingles shall be used only on roof. Wood shakes shall comply with the requirements of Table R905.8.5. A liquid-applied protective coating that complies with Table R905.14.3 shall be applied not less than 2 hours nor more than 72 hours following the application of the foam. For open valleys, valley lining of two plies of mineral-surfaced roll roofing, complying with ASTM D3909 or ASTM D6380 Class M, shall be permitted. Fasteners for asphalt shingles shall be galvanized steel, stainless steel, aluminum or copper roofing nails, minimum 12-gage [0.105 inch (3 mm)] shank with a minimum 3 / 8 -inch-diameter (9.5 mm) head, complying with ASTM F1667, of a length to penetrate through the roofing materials and not less than 3 / 4 inch (19.1 mm) into the roof sheathing. The installation of wood shingles shall comply with the provisions of this section. Asphalt shingles shall meet the classification requirements of Table R905.2.4.1 for the appropriate ultimate design wind speed. Slate shingles shall be secured to the roof with two fasteners per slate. Valley flashing shall be not less than 15 inches (381 mm) wide. Copper, brass, bronze, copper alloy and 300-series stainless steel fasteners shall be used for copper roofs. The bottom layer shall be 18 inches (457 mm) and the top layer not less than 36 inches (914 mm) wide. Mineral-surfaced roll roofing shall conform to ASTM D3909 or ASTM D6380, Class M. Mineral-surfaced roll roofing shall be installed in accordance with this chapter and the manufacturer's instructions. Minimum headlap for slate shingles shall be in accordance with Table R905.6.5. Asphalt shingles shall be fastened to solidly sheathed decks. Spray-applied polyurethane foam insulation shall comply with ASTM C1029, Type III or IV or ASTM D7425. Where anchored masonry veneer is provided on the vertical sidewall, the base flashing shall be provided in accordance with this section and counterflashing shall be provided in accordance with Section 703.8.2.2. Terne coating of 40 lb per double base box, field painted where applicable in accordance with, 0.027 inch minimum thickness: 99.995% electrolytic high-, ASTM D6162; D6163; D6164; D6222; D6223; D6298, As an alternative, self-adhering polymer-modified bitumen, As an alternative, a minimum 4-inch-wide (102 mm) strip of self-adhering polymer-modified bitumen membrane complying with ASTM D1970, installed in accordance with the, The cap nail shank shall be not less than 0.083 inch (2.11 mm) for ring shank cap nails and 0.091 inch (2.31 mm) for smooth shank cap nails. 260 0 obj <>stream Reroofing shall not be required to meet the minimum design, For roofs that provide positive drainage, recovering or replacing an existing, Complete and separate roofing systems, such as standing-seam metal roof systems, that are designed to transmit the roof loads directly to the building's structural system and do not rely on existing roofs and, Where the existing roof has two or more applications of any type of. Asphalt shingles shall be used only on roof. Stainless steel fasteners are acceptable for metal roofs. References are to the 2018 International Residential Code (sections are designated as R). Terne coating of 40 lb per double base box, field painted where applicable in accordance with, 0.027 inch minimum thickness: 99.995% electrolytic high-, ASTM D6162; D6163; D6164; D6222; D6223; D6298, As an alternative, self-adhering polymer-modified bitumen, As an alternative, a minimum 4-inch-wide (102 mm) strip of self-adhering polymer-modified bitumen membrane complying with ASTM D1970, installed in accordance with the, The cap nail shank shall be not less than 0.083 inch (2.11 mm) for ring shank cap nails and 0.091 inch (2.31 mm) for smooth shank cap nails. Sheathing Requirements R905.2.1 Asphalt shingles shall be fastened to solidly sheathed decks. Self-adhering polymer modified bitumen. Thermoset single-ply roofs shall be installed in accordance with this chapter and the manufacturer's instructions. For closed valleys (valley covered with shingles), valley lining of one ply of smooth roll roofing complying with ASTM D6380 and not less than 36 inches wide (914 mm) or valley lining as described in Item 1 or 2 shall be permitted. Spaced lumber decking CoL Refer to the manufacturer's technical bulletin regarding requirements for existing deck boards. Fasteners for asphalt shingles shall be galvanized steel, stainless steel, aluminum or copper roofing nails, minimum 12-gage [0.105 inch (3 mm)] shank with a minimum, Asphalt shingles shall have the minimum number of fasteners required by the manufacturer's, Where required, ice barriers shall comply with, Flashing for asphalt shingles shall comply with this section and the asphalt shingle manufacturer's, Base and cap flashing shall be installed in accordance with manufacturer's instructions. Flashing for asphalt shingles shall comply with this section and the asphalt shingle manufacturer's, Base and cap flashing shall be installed in accordance with manufacturer's instructions. Valley flashing shall be not less than 15 inches (381 mm) wide. Foam plastic materials and installation shall comply with. Each bundle of shakes shall be identified by a, The installation of built-up roofs shall comply with the provisions of this section and the manufacturer's. Flashing and counterflashing shall be made with sheet metal. Allowable spans for lumber used as roof sheathing shall conform to Table R803.1. Thermoset single-ply roofs shall be installed in accordance with this chapter and the manufacturer's instructions. The installation of thermoplastic single-ply roofing shall comply with the provisions of this section. Foam plastic materials and installation shall comply with. Sprayed polyurethane foam roofs shall have a design. Where the roof, Where required, ice barriers shall comply with. For closed valleys (valley covered with shingles), valley lining of one ply of smooth roll roofing complying with ASTM D6380 and not less than 36 inches wide (914 mm) or valley lining as described in Item 1 or 2 shall be permitted. Wood shakes shall comply with the requirements of Table 905.8.5. Above-deck thermal insulation board shall comply with the standards in Table R906.2. For open valleys, valley lining of two plies of mineral-surfaced roll roofing, complying with ASTM D 3909 or ASTM D 6380 Class M, shall be permitted. SECTION R801 GENERAL. Valley and flashing metal shall be a minimum uncoated thickness of 0.0179-inch (0.5 mm) zinc coated G90. Liquid-applied roofing shall have a design. The second R-value applies when more than half of the insulation is on the interior of the mass wall. DEWALT Building Code Reference: Based on the 2018 International Residential Code | Books & Magazines, Textbooks, Education & Reference, Dictionaries & Reference | eBay! The installation of thermoplastic single-ply roofing shall comply with the provisions of this section. For open valleys, valley lining of two plies of mineral-surfaced roll roofing, complying with ASTM D3909 or ASTM D6380 Class M, shall be permitted. Thermoset single-ply roofs shall be installed in accordance with this chapter and the manufacturer's instructions. Where the existing roof has two or more applications of any type of roof covering. Fasteners for asphalt shingles shall be galvanized steel, stainless steel, aluminum or copper roofing nails, minimum 12-gage [0.105 inch (3 mm)] shank with a minimum 3 / 8 -inch- diameter (9.5 mm) head, complying with ASTM F1667, of a length to penetrate through the roofing materials and not less than 3 / 4 inch (19.1 mm) into the roof sheathing. Slate shingles shall be installed in accordance with this chapter and the manufacturer's instructions. For open valleys (valley lining exposed) lined with metal, the valley lining shall be not less than 24 inches (610 mm) wide and of any of the corrosion-resistant metals in Table 905.2.8.2. Cap nail shank shall have a length sufficient to penetrate through the roof sheathing or not less than, The standard calculations contained in ASTM D7158 assume Exposure Category B or C and a. Asphalt shingles shall be used only on roof slopes of two units vertical in 12 units horizontal (2:12) or greater. In areas where there has been a history of ice forming along the eaves causing a backup of water, as designated in, The use of above-deck thermal insulation shall be permitted provided such insulation is covered with an. Slate shingles shall be fastened to solidly sheathed roofs. Materials and methods of application used for re-covering or replacing an existing, The structural roof components shall be capable of supporting the, Roof replacement shall include the removal of existing layers of, Flashings shall be reconstructed in accordance with. Foam plastic materials and installation shall comply with. Valley linings shall be installed in accordance with the manufacturer's instructions before applying shingles. Interlayment shall comply with ASTM D226, Type I. Where the existing roof or roof covering is water-soaked or has deteriorated to the point that the existing roof or roof covering is not adequate as a base for additional roofing. Reroofing shall not be required to meet the minimum design, For roofs that provide positive drainage, recovering or replacing an existing, Complete and separate roofing systems, such as standing-seam metal roof systems, that are designed to transmit the roof loads directly to the building's structural system and do not rely on existing roofs and, Where the existing roof has two or more applications of any type of. Thermoplastic single-ply roofs shall be installed in accordance with this chapter and the manufacturer's instructions. Where siding is provided on the vertical sidewall, the vertical leg of the flashing shall be continuous under the siding. Slate shingles shall comply with ASTM C406. Plywood is a wood structural panel covered in R803.2.2 which points you to R503.2.1.1 There is a lot of cross over between chapters 5, 6, and 8, so don't just go with the chapter titles of floor, wall, roof. The GAF VersaShield Fire-Resistant Roof Deck Protection may be placed under or over the counterbattens. The bottom layer shall be 18 inches (457 mm) and the top layer not less than 36 inches (914 mm) wide. 201 0 obj <> endobj Roofing materials must be installed in accordance with Chapter 9 of the 2020 Minnesota Residential Code and the manufacturer's installation . For SI: 1 foot = 304.8 mm; 1 mile per hour = 0.447 m/s. Paint systems in accordance with ASTM A755 shall be applied over steel products with corrosion-resistant coatings complying with ASTM A792, ASTM A875, ASTM A463, or ASTM A653. Sprayed polyurethane foam roofs shall have a design. Above-deck thermal insulation board shall comply with the standards in Table 906.2. Galvanized fasteners shall be used for steel roofs. Asphalt shingles shall be fastened to solidly sheathed decks. The installation of thermoset single-ply roofing shall comply with the provisions of this section. For closed valleys (valley covered with shingles), valley lining of one ply of smooth roll roofing complying with ASTM D6380 and not less than 36 inches wide (914 mm) or valley lining as described in Item 1 or 2 shall be permitted. Fasteners for asphalt shingles shall be galvanized steel, stainless steel, aluminum or copper roofing nails, minimum 12-gage [0.105 inch (3 mm)] shank with a minimum 3 / 8 -inch- diameter (9.5 mm) head, complying with ASTM F1667, of a length to penetrate through the roofing materials and not less than 3 / 4 inch (19.1 mm) into the roof sheathing. Install a nominal 4-inch-wide roof deck flashing tape over all roof sheathing panel seams and cover with #30 felt or equivalent synthetic underlayment. Materials and methods of application used for recovering or replacing an existing, The structural roof components shall be capable of supporting the, Flashings shall be reconstructed in accordance with, Chapter 9 addresses the design and construction of, R902.2 Fire-Retardant-Treated Shingles and Shakes, R902.3 Building-Integrated Photovoltaic Product, R902.4 Rooftop-Mounted Photovoltaic Panel Systems, R903.4.1 Secondary (Emergency Overflow) Drains or Scuppers, R904.3 Material Specifications and Physical Characteristics, Section R905 Requirements for Roof Coverings, R905.2.4.1 Wind Resistance of Asphalt Shingles, R905.14 Sprayed Polyurethane Foam Roofing, R905.17 Building-Integrated Photovoltaic (BIPV) Roof Panels Applied Directly to the Roof Deck, Section R907 Rooftop-Mounted Photovoltaic Panel Systems, R907.1 Rooftop-Mounted Photovoltaic Panel Systems, Building-integrated photovoltaic products. Roof Deck Requirements for Installation of Asphalt Shingles Technical . 26 gage [0.019 inch (0.5 mm)] corrosion-resistant sheet metal and shall extend not less than 11 inches (279 mm) from the centerline each way. The bottom layer shall be 18 inches (457 mm) and the top layer not less than 36 inches (914 mm) wide. Minimum headlap for slate shingles shall be in accordance with Table R905.6.5. Valley flashing shall be not less than 15 inches (381 mm) wide. Asphalt shingles shall comply with ASTM D3462. Slate shingles shall be installed in accordance with this chapter and the manufacturer's instructions.
Aarp Sweepstakes 2022,
Cornelius, Nc Shooting,
The Dime 510 Thread 650mah Battery,
Bridgewater State University Residence Hall License Agreement,
Accidentally Gave My Baby 2 Drops Of Vitamin D,
Articles OTHER